1. All the busbars & busbar supports are designed to
withstand necessary short circuit levels the size of the
busbar insulator distance between insulator is designed to
carry rated currents at 50 degree centigrade ambient with
maximum Temperature rise of 30 degree centigrade.
2. Necessary precaution is taken for busbar just including
cleaning by sandpaper & application of petroleum jelly for
protection against oxidation (for Aluminum busbar only)
3. The number of hole in the busbar is kept to petroleum
jelly for is kept to minimum. The loss in using additional
cross selection of busbar completeness area.
4. The joint of busbar have sufficient overlaps or
additional strips.
5. The busbar supports are usually of SMC & DMC.
6. The complete busbar system is independently supported so
that no load Can transferred to switch gear components.
7. The bending of busbar is done using hydraulic machine so
that no cracks are developed & deformation is minimum.
8. Suitable spacing is maintained between the busbars
9. The busbars are insolated with the heat shrinkable
sleeves.
10. Wherever necessary the busbar is shrouded to avoided the
human touch.